Battery Runtime Analysis Report
Generated on May 18, 2025
UPS & Emergency Power System Analysis
Battery System Configuration
Battery Type: Lithium Iron Phosphate (LiFePO4)
Configuration: Series Parallel
Total Batteries: 16
Series Count: 4
Parallel Count: 4
System Voltage: 51.2 V
Total Capacity: 400 Ah
Runtime Analysis
Runtime: 4 hours 12 minutes
Total Load: 4800 W
Average Current: 93.75 A
Usable Energy: 19,456 Wh
Depth of Discharge: 95%
System Efficiency: 91.2%
Load Analysis
DC Load
5333 W
AC Load
4800 W
Current per Battery
23.44 A
Efficiency Breakdown
Loss Factor | Loss Percentage | Efficiency |
---|---|---|
Inverter Loss | 5.0% | 95.0% |
Battery Loss | 4.0% | 96.0% |
Temperature Loss | 0.0% | 100.0% |
Aging Loss | 0.0% | 100.0% |
Total System | 8.8% | 91.2% |
Recommendations
- • Consider adding more batteries in parallel to increase runtime.
- • Implement load shedding for non-critical equipment to extend runtime.
- • Monitor individual battery performance in large parallel strings.
- • Consider high-efficiency inverter to reduce power losses.
Calculation Notes
• Runtime calculations include Peukert effect for battery type
• Efficiency losses are applied cumulatively
• Depth of discharge limit protects battery life
• Temperature and aging factors affect available capacity
• Actual runtime may vary based on load profile and conditions
Report generated by Electric Tools Suite
Professional electrical calculation tools