Conduit Fill Calculation - EMT

Conduit Fill Calculator • Example Report

Conduit Fill Calculation Report

Generated on May 17, 2025

NEC Chapter 9 Compliance Analysis

Conduit Specifications

Conduit Type: EMT

Trade Size: 1-1/2"

Internal Area: 2.036 sq.in.

Installation Type: Raceway

Fill Type: Standard

Fill Analysis

Total Wire Area: 0.7623 sq.in.

Fill Percentage: 37.4%

Allowed Fill: 40%

Remaining Area: 0.0518 sq.in.

NEC Compliant: Yes

Wire Breakdown

Wire Type AWG Size Count Individual Area (sq.in.) Total Area (sq.in.) % of Total
THHN 12 AWG 15 0.0133 0.1995 26.17%
THHN 10 AWG 8 0.0211 0.1688 22.14%
THHN 8 AWG 4 0.0366 0.1464 19.21%
THHN 6 AWG 5 0.0507 0.2535 33.25%

Recommendations

  • • Fill percentage (37.4%) is close to the NEC limit (40%). Consider using a larger conduit for future expansion.
  • • Multiple wire types detected. Ensure compatibility and temperature ratings.
  • • Large number of conductors may require derating per NEC 310.15(C)(1).

NEC Requirements

• Fill calculations per NEC Chapter 9, Tables 4 and 5

• Maximum fill: 53% (1 conductor), 31% (2 conductors), 40% (3+ conductors)

• Nipples 24" or less allow 60% fill for 2 or more conductors

• Wire areas include insulation thickness per conductor type

• Conduit areas are internal cross-sectional areas