Voltage Drop Analysis - 200A Service

Voltage Drop Calculator • Example Report

Voltage Drop Calculation Report

Generated on May 15, 2025

Circuit Parameters

System Type: Single-Phase

Supply Voltage: 240 V

Load Current: 200 A

Circuit Distance: 150 ft

Conductor Material: Copper

Wire Size: 2/0 AWG

Power Factor: 0.95

Calculation Results

Voltage Drop: 5.89 V

Voltage Drop %: 2.45%

Voltage at Load: 234.11 V

Power Loss: 1178 W

Within Limits: Yes (≤3%)

Calculation Method

Formula Used:

Single-Phase: VD = 2 × I × R × L × PF

Where: VD = Voltage Drop, I = Current, R = Resistance, L = Length, PF = Power Factor

Code Compliance Notes

• NEC recommends maximum 3% voltage drop for branch circuits

• Total voltage drop (feeders + branch circuits) should not exceed 5%

• Voltage drop affects motor starting and equipment performance

• Consider load growth and future expansion when sizing conductors